Healthcare


Cape Henlopen Medical Office Building

Paragon Engineering Corporation provide design for two separate multi-tenant medical office building. The design included design of the shell and core heating, ventilation and air conditioning system and fitout of the building based on the actual planned usage of the tenants. Two VRF heat pumps were installed on the roof of each building, 88 tons of capacity for the Enterprise MOB and 80 tons of capacity for the Cape Henlopen MOB. The occupied space was conditioned using both ceiling cassette air handlers and concealed ducted air handlers. Refrigerant piping was designed between the heat pumps and air handlers.

Dedicated outside air units were used to provide fresh air to the occupied space. In rooms with ceiling cassettes the air was supply directly to the room at a natural temperature not to upset the comfort of the space. For spaces that were conditioned using concealed units the fresh air was connected to the return of the air handlers.

The VRF systems provide highly efficient, flexible heating, ventilation and air conditioning for the building.

MRI Suite – The fitout of each building included the fitout of an MRI suite. The suites were about 3,000 square feet. All the space except for the MRI equipment room was served by the house VRF system. Because of the high equipment load a separate 10-ton, cooling only VRF system was designed for the MRI equipment room.

The MRI suite presented some special challenges that were met by the design team. The MRI equipment had a remote air-cooled chiller that had to be located outdoors and interconnected with the MRI equipment. All materials in the MRI Room below the RF Screen had to be non-ferrous materials. Additionally, the cryogen emergency relief had to be designed to relieve safety outdoors to meet the manufacturer’s back-pressure restraints.

Abby Medical Center

Shell and Core MEP design for a new 3 story, 75,000 SF medical office building. The building houses several General Practice suites, medical laboratories, and a future surgi-center.

The Chester County Hospital
Fern Hill

75,000 sq. ft. Design of HVAC, plumbing, fire protection and electrical systems for the new medical arts facility including Professional Offices, Medical Laboratory, Imaging Center and Medical Clinic.

Park Stream Medical Center

Shell and Core MEP design for a new two-story 16,000 sq. ft. medical office building.

Limestone II Professional Building

35,000 sq. ft. Design of HVAC, plumbing, fire protection and electrical systems for the new medical arts facility including Professional Offices, Medical Laboratory, Imaging Center and Medical Clinic.

Riverside Hospital
Medical Arts Building

35,000 sq. ft. Design of the shell and core HVAC, plumbing, fire protection and electrical systems for a new out-patient support facility.

Glasgow Medical Center

60,000 sq. ft. Design of HVAC, plumbing, fire protection and electrical systems for the new medical arts facility including Professional Offices, Medical Laboratory, Imaging Center and Medical Clinic.

Abby Medical Center
Doctor’s office fit-out

MEP fit-out for a 5,500 sq. ft. doctor’s office suite. The suite included exam rooms, offices, and out-patient procedure rooms.

MDS Pharmaceutical
Renaissance Center

MEP tenant fit-out of 76,500 SF including general offices, conference room, LAN room, support areas, etc.

Kennett Medical Center

30,000 sq. ft. Design of HVAC, plumbing, fire protection and electrical systems for the outpatient medical facility.

Abby Medical Center
Dynamic Physical Therapy

Fit-out for a physical therapy space including a therapy pool.

Abby Medical Center
Lab Corp

Fit-out of a laboratory facility.

Union Hospital
Adult Daycare Center

MEP design of a new 7,000 SF adult daycare facility.

Neurosciences

MEP shell and core and fitout for Medical Office Building Suite. The fit-out consisted of 5 General Practice suites, a pharmacy and a medical laboratory.

Nemours Health Services Offices

Provide M&E office space fit-out of approximately 25,000 square feet of existing building space.

University of Delaware
Medical Technology Building

Renovations to Willard Hall to convert for use by the Medical Technology department.

Riverside Medical Arts Building
Renal Treatment Center

Design of HVAC, plumbing and electrical systems for a fifteen-station, outpatient dialysis facility.

Stine/Haskell Medical Facility

5,000 sq. ft. Design of HVAC, plumbing and electrical systems for an on-site, outpatient and emergency care facility for DuPont’s Stine/Haskell Laboratory Site.

Wilmington Hospital

Design of modifications for the operating rooms to provide automatic HVAC energy conservation during unoccupied periods through the use of motion detectors. This project was for the Medical Center of Delaware.

Christiana Hospital

Design of modifications for the operating rooms to permit HVAC energy conservation during unoccupied periods. This project was for the Medical Center of Delaware.

Wilmington Hospital

Creation of electronic record drawings for the water and gas systems. This work was accomplished through investigation of existing drawings and field survey. This project was for the Medical Center of Delaware.

Wilmington Hospital

Design of the mechanical and electrical system for conversion of the existing oil fire burners to gas fired. This project was for the Medical Center of Delaware.

Christiana Hospital

Conversion of the hospital’s central air handling units from variable air volume control through inlet dampers to variable frequency motor drives. This project was for the Medical Center of Delaware.

Christiana Hospital

Computerized hydraulic analysis of the existing chilled water system. Recommendations formulated from this analysis improved the performance of the existing system. This project was for the Medical Center of Delaware.

Riverside Hospital
Emergency Care

Schematic design of the mechanical and electrical facilities for emergency care addition.

Riverside Hospital

Design of the mechanical and electrical facilities for the replacement of the primary cooling tower.

Christiana Hospital

Design of upgrades to existing parking lot lighting system to increase illumination levels for safety and use of security surveilence cameras.

Limestone Professional Building

Design of upgrades to the Life Safety systems (exit and egress lighting) and ADA upgrades.

Wilmington Hospital

Design of mechanical and electrical systems for the replacement of the central chiller unit.

DuPont Stine Lab
Medical Facilities

Design of mechanical and electrical systems for the on-site medical facility.

Henrietta Johnson Medical Center

Design of HVAC, plumbing, fire protection and electrical systems for the new medical arts facility including Professional Offices, Medical Laboratory, Imaging Center and Medical Clinic.

Christiana Hospital

Design of mechanical and electrical systems for the x-ray area in the education building.

Wilmington Hospital

Design of MEP systems for the 7th floor Endoscopy area.

Christiana Hospital

Design of the mechanical and electrical systems for the microbiology area at the hospital.

Christiana Hospital

Study of MEP systems for tuberculosis area.

Wilmington Hospital

Design of the mechanical and electrical systems for the hospitals pain center.

Silverside Road Medical Office Building

Mechanical and electrical fit-out for a medical office suite.

Share this: